110 Part Number STH038 5/12
Suction Temperature High Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
page 102
Discharge Temperature
Discharge temperature is too high and is affecting
suction temperature – refer to “Freeze Cycle
Discharge Temperature High Checklist”
(page 107)
Improper Refrigerant Charge
Overcharged (also see “Freeze Cycle Discharge
Temperature High Checklist” page 107)
Wrong type of refrigerant
Non condensable in system
Components
Harvest valve leaking - continue the table
TXV flooding - continue the table
Defective compressor - continue the table
Other
Non-Manitowoc components in system