Part Number STH025 2/14 203
Refrigerant Recovery/Evacuation
SELF-CONTAINED MODEL PROCEDURE
Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the
manufacturer’s recommendations.
Connections
Manifold gauge sets must utilize low loss fittings to
comply with U.S. Government rules and regulations.
Make these connections:
Suction side of the compressor through the suction
service valve.
Discharge side of the compressor through the
discharge service valve.
Important
Manitowoc assumes no responsibility for the use of
contaminated refrigerant. Damage resulting from the
use of contaminated refrigerant is the sole
responsibility of the servicing company.
Important
Replace the liquid line drier after recovering the
refrigerant and before evacuating and recharging.
Use only a Manitowoc (OEM) liquid line filter-drier to
prevent voiding the warranty.