Manitowoc Q130 Dokumentacja Strona 153

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 152
Part Number 80-01111-9 7/10 153
Suction Pressure High Checklist
Improper Installation
Refer to “Installation and Visual Inspection
Checklist” on page 104.
Discharge Pressure
Discharge pressure is too high, and is affecting
suction pressure, refer to “Discharge Pressure
High Checklist” on page 150.
Improper Refrigerant Charge
Overcharged
Wrong type of refrigerant
Non-condensables in system
Other
Non-Manitowoc components in system
Hot gas valve leaking
Defective compressor
Water inlet valve leaking
Suction Pressure Low Checklist
Improper Installation
Refer to “Installation and Visual Inspection
Checklist” on page 104.
Discharge Pressure
Discharge pressure is too low, and is affecting
suction pressure, refer to Freeze Cycle Discharge
Pressure Low Checklist” on page 150.
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Przeglądanie stron 152
1 2 ... 148 149 150 151 152 153 154 155 156 157 158 ... 235 236

Komentarze do niniejszej Instrukcji

Brak uwag