Manitowoc NEO UD0310AE Dokumentacja Strona 93

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 92
Part Number STH042 3/14 93
4
The harvest valve
inlet is
COOL
and
The compressor
discharge line is
HOT
Discharge line
temp 150°F
(66°C) or higher
at the end of
freeze cycle
Compressor
3
The harvest valve
inlet is
COOL
and
The compressor
discharge line is
COOL
Discharge line
temp less than
150°F (66°C) at
the end of freeze
cycle
TXV Flooding
2
The harvest valve
inlet is
COOL
and
The compressor
discharge line is
HOT
Discharge line
temp 150°F
(66°C) or higher
at the end of
freeze cycle
Low On Charge
-or-
TXV Starving
1
The harvest valve
inlet is
HOT
and
The compressor
discharge line is
HOT
Discharge line
temp 150°F
(66°C) or higher
at the end of
freeze cycle
Harvest Valve
Leaking
Operational Analysis
harvest Valve
Discharge Line Temp.
Record freeze cycle
discharge line temp at the
end of freeze cycle.
Final Analysis
Enter total number of
boxes checked in
each column.